INDOOR AIR QUALITY ASSESSMENT 
Winthrop Elementary School 
65 Central Street 
Ipswich, Massachusetts 01938 
Prepared by: 
Massachusetts Department of Public Health 
Bureau of Environmental Health 
Indoor Air Quality Program 
October 2009

Background/Introduction 
At the request of Paul Bedard, Facilities Maintenance/Custodial Supervisor for Ipswich 
Public Schools, the Massachusetts Department of Public Health (MDPH), Bureau of 
Environmental Health (BEH) provided assistance and consultation regarding indoor air quality at 
the Winthrop Elementary School (WES) located at 65 Central Street, Ipswich , Massachusetts. 
BEH staff made an initial visit to the school in November 2008 to examine conditions at the 
school. On June 12, 2009, James Tobin, Environmental Analyst/Inspector in BEH’s Indoor Air 
Quality Program, returned to the school to conduct air testing. 
The WES is a two-story, brick building built in 1957 on a slab foundation. In 1987, an 
addition was built expanding the western side of the building. A modular classroom building 
was installed for use 12 years ago. The school houses general classrooms, a library, gymnasium, 
cafeteria/auditorium, art room, music room and office space. Windows are openable throughout 
the building. 
Methods 
Air tests for carbon dioxide, temperature, relative humidity and carbon monoxide were 
conducted with the TSI, Q-Trak, IAQ Monitor, Model 7565. Air tests for airborne particle 
matter with a diameter less than 2.5 micrometers were taken with the TSI, DUSTTRAK™ 
Aerosol Monitor Model 8520. BEH staff also performed visual inspection of building materials 
for water damage and/or microbial growth. 
2

Results 
The school houses approximately 450 students in grades pre-K through 5 with 
approximately 40 staff members. Tests were taken during normal operations at the school and 
results appear in Table 1. 
Discussion 
Ventilation 
It can be seen from Table 1 that carbon dioxide levels were above 800 parts per million 
(ppm) in 14 of 35 areas, indicating inadequate air exchange in 40% of the areas evaluated at the 
time of the assessment. It is also important to note that a number of areas had open windows or 
were empty/sparsely populated, both of which can greatly reduce carbon dioxide levels. Carbon 
dioxide levels would be expected to increase with higher occupancy and windows closed. 
Fresh air for classrooms is supplied by unit ventilator (univent) systems (Picture 1). A 
univent draws outdoor air through a fresh air intake located on the exterior wall of the building 
(Picture 2), and return air from the room through an air intake located at the base of the unit 
( Figure 1 ). Fresh and return air are mixed, filtered, heated and distributed to the room through an 
air diffuser located in the top of the unit. Univents were operating in the majority of rooms at the 
time of the assessment; however, BEH staff found several univents switched ‘off’, preventing 
fresh air from being introduced into these rooms. Univent air diffusers and returns were blocked 
by furniture and other stored items in front and on top of the unit, thereby limiting airflow in 
these rooms. In one area, the univent had a missing panel exposing the interior of the unit 
(Picture 3). In order for univents to provide fresh air as designed, air diffusers, intakes and 
returns must remain free of obstructions. Importantly, these units must remain “on” and be 
3

allowed to operate while rooms are occupied. A univent operating in a mode that provides a 
continual supply of fresh, outdoor air can improve both indoor air quality and comfort, since this 
continual source of fresh air dilutes pollutants that typically accumulate in indoor environments. 
Exhaust ventilation is provided by vents ducted to rooftop motors. Exhaust vents at the 
WES are located on the ceiling, wall, or at the top of storage closets/shelving (Pictures 4 through 
7). Exhaust ventilation systems continuously remove air that has become stale from moisture, 
odors, and pollutants. In order to function properly, exhaust vents must be activated and allowed 
to operate without obstruction while rooms are occupied. Without adequate exhaust ventilation, 
excess heat and stale air can build up leading to indoor air quality and comfort complaints. The 
work room is not equipped with exhaust ventilation. This area contains photocopiers and a 
lamination machine each of which can be a source of pollutants such as heat and odors, 
particularly if the equipment is older and in frequent use. 
Wall-mounted air handling units (AHUs) provide ventilation for the modular classroom 
wing (Picture 8). The modular wing houses three rooms; however, only two AHUs exist. One 
room lacks mechanical ventilation; therefore, windows and an exterior door are the only means 
of introducing fresh air to this area. AHUs draw fresh air through an air intake on the exterior of 
the modular classroom and then distribute it to the room through an air diffuser at the top of the 
AHU. Stale air from the room is returned to the AHU through a vent at the base of the unit to an 
exhaust vent on the building exterior. Thermostats that control the AHU system in the modular 
classrooms have fan settings of “on” and “automatic”. The “automatic” setting on the thermostat 
activates the AHU system at a preset temperature, and then deactivates the system once the 
preset temperature is reached. In the fan “on” setting, the AHU system provides continuous 
airflow to the rooms. 
4

On the exterior wall of the modular classroom, the fresh air intake is directly above the 
exhaust vent (Picture 9). The configuration of the intake and vent is problematic since pollutants 
that are exhausted from the classroom can be brought back inside via the air intake . The exhaust 
vent should be ducted away from the fresh air intake. BEH staff also found the fresh air intakes 
coated with accumulated dust and debris (Picture 10). 
Air conditioners (AC) were used in several rooms (Pictures 11 and 12). ACs are 
normally equipped with filters, which should be cleaned or changed as per manufacturers’ 
instructions to avoid the build-up and re-aerosolization of dirt, dust and particulate matter. 
To maximize air exchange, the MDPH recommends that both supply and exhaust 
ventilation operate continuously during periods of school occupancy. In order to have proper 
ventilation with a mechanical supply and exhaust system, the systems must be balanced to 
provide an adequate amount of fresh air to the interior of a room while removing stale air from 
the room. It is recommended that heating, ventilating and air conditioning (HVAC) systems be 
re-balanced every five years to ensure adequate air systems function (SMACNA, 1994). 
The Massachusetts Building Code requires that each room have a minimum ventilation 
rate of 15 cubic feet per minute (cfm) per occupant of fresh outside air or openable windows 
(SBBRS, 1997; BOCA, 1993). The ventilation must be on at all times that the room is occupied. 
Providing adequate fresh air ventilation with open windows and maintaining the temperature in 
the comfort range during the cold weather season is impractical. Mechanical ventilation is 
usually required to provide adequate fresh air ventilation. 
Carbon dioxide is not a problem in and of itself. It is used as an indicator of the adequacy 
of the fresh air ventilation. As carbon dioxide levels rise, it indicates that the ventilating system 
is malfunctioning or the design occupancy of the room is being exceeded. When this happens, a 
5

buildup of common indoor air pollutants can occur, leading to discomfort or health complaints. 
The Occupational Safety and Health Administration (OSHA) standard for carbon dioxide is 
5,000 parts per million parts of air (ppm). Workers may be exposed to this level for 40 
hours/week, based on a time-weighted average (OSHA, 1997). 
The MDPH uses a guideline of 800 ppm for publicly occupied buildings. A guideline of 
600 ppm or less is preferred in schools due to the fact that the majority of occupants are young 
and considered to be a more sensitive population in the evaluation of environmental health 
status. Inadequate ventilation and/or elevated temperatures are major causes of complaints such 
as respiratory, eye, nose and throat irritation, lethargy and headaches. For more information 
concerning carbon dioxide, consult Appendix A . 
Indoor temperature measurements ranged from 66 o F to 70 o F, which were below or at the 
lower end of the MDPH recommended comfort range (Table 1). The MDPH recommends that 
indoor air temperatures be maintained in a range of 70 o F to 78 o F in order to provide for the 
comfort of building occupants. In many cases concerning indoor air quality, fluctuations of 
temperature in occupied spaces are typically experienced, even in a building with an adequate 
fresh air supply. In addition, it is difficult to control temperature and maintain comfort without 
operating the ventilation equipment as designed (e.g., univents deactivated/obstructed). 
The relative humidity in the building ranged from 58 to 75 percent, which was above the 
MDPH recommended comfort range in some areas (Table 1). The MDPH recommends a 
comfort range of 40 to 60 percent for indoor air relative humidity. Elevated indoor relative 
humidity would be expected in a building that, with the exception of select areas, lacks AC to 
remove excess moisture from the air on a day when outdoor relative humidity is 80 to 90 percent 
(Table 1). Without a dehumidification system or central AC, indoor relative humidity is difficult 
6

to maintain in a comfort range when outdoor relative humidity is high. Relative humidity levels 
in the building would be expected to drop during the winter months due to heating. The 
sensation of dryness and irritation is common in a low relative humidity environment. Low 
relative humidity is a very common problem during the heating season in the northeast part of 
the United States. 
Microbial/Moisture Concerns 
In order for building materials to support mold growth, a source of water exposure is 
necessary. Identification and elimination of the source of water moistening building materials is 
necessary to control mold growth. BEH staff examined the building to identify breaches in the 
building envelope that could provide a source of water penetration. 
BEH staff examined the building to identify breaches in the building envelope that could 
provide a source of water penetration. BEH identified the following conditions that could lead to 
water penetration: 
 Shrubs and trees growing against the building, holding moisture against exterior brick 
(Pictures 13 through 15); 
 Plants and shrubs growing in front of fresh air intakes allowing moisture-laden air to be 
drawn in by the fresh air intake (Pictures 15 through 17); and, 
 Exterior brick was damaged and water stained indicating a heavy and/or continuous water 
exposure (Pictures 18 and 19). 
These conditions indicate that water has penetrated through the building envelope. Moisture 
laden air can infiltrate through breaches and condense on building materials. A heavy and/or 
continuous water exposure to the building exterior can undermine the integrity of the building 
7

envelope and provide a means of water entry into the building via capillary action through 
foundation concrete (i.e., cement slab) and masonry (Lstiburek & Brennan, 2001). 
A number of rooms had water-damaged ceiling tiles, which can indicate leaks from the 
roof, plumbing system or through the building envelope. Water-damaged ceiling tiles can 
indicate sources of water penetration and provide a source of mold growth. Ceiling tiles should 
be replaced after a water leak is discovered and repaired. 
The US Environmental Protection Agency (US EPA) and the American Conference of 
Governmental Industrial Hygienists (ACGIH) recommend that porous materials be dried with 
fans and heating within 24 to 48 hours of becoming wet (US EPA, 2001; ACGIH, 1989). If not 
dried within this time frame, mold growth may occur. Once mold has colonized porous 
materials, they are difficult to clean and should be removed and discarded. 
A number of classrooms had plants (Picture 20). Plants can be a source of pollen and 
mold, which can be respiratory irritants for individuals. Plants should be properly maintained 
and equipped with drip pans to prevent water damage to porous building materials, which can 
lead to mold growth. Plants should also be located away from ventilation sources (e.g., air 
intakes, univent diffusers) to prevent the entrainment and/or aerosolization of dirt, pollen or 
mold. 
Aquariums were also located in a number of classrooms (Picture 21). Aquariums should 
be properly maintained to prevent microbial/algae growth, which can emit unpleasant odors. 
Other IAQ Evaluations 
Indoor air quality can be negatively influenced by the presence of respiratory irritants, 
such as products of combustion. The process of combustion produces a number of pollutants. 
Common combustion emissions include carbon monoxide, carbon dioxide, water vapor and 
8

smoke (fine airborne particle material). Of these materials, exposure to carbon monoxide and 
particulate matter with a diameter of 2.5 micrometers (μm) or less (PM2.5) can produce 
immediate, acute health effects upon exposure. To determine whether combustion products were 
present in the school environment, BEH staff obtained measurements for carbon monoxide and 
PM2.5. 
Carbon Monoxide 
Carbon monoxide is a by-product of incomplete combustion of organic matter (e.g., 
gasoline, wood and tobacco). Exposure to carbon monoxide can produce immediate and acute 
health affects. Several air quality standards have been established to address carbon monoxide 
and prevent symptoms from exposure to these substances. The MDPH established a corrective 
action level concerning carbon monoxide in ice skating rinks that use fossil-fueled ice 
resurfacing equipment. If an operator of an indoor ice rink measures a carbon monoxide level 
over 30 ppm, taken 20 minutes after resurfacing within a rink, that operator must take actions to 
reduce carbon monoxide levels (MDPH, 1997). 
The American Society of Heating Refrigeration and Air-Conditioning Engineers 
(ASHRAE) has adopted the National Ambient Air Quality Standards (NAAQS) as one set of 
criteria for assessing indoor air quality and monitoring of fresh air introduced by HVAC systems 
(ASHRAE, 1989). The NAAQS are standards established by the US EPA to protect the public 
health from six criteria pollutants, including carbon monoxide and particulate matter (US EPA, 
2006). As recommended by ASHRAE, pollutant levels of fresh air introduced to a building 
should not exceed the NAAQS levels (ASHRAE, 1989). The NAAQS were adopted by 
reference in the Building Officials & Code Administrators (BOCA) National Mechanical Code 
of 1993 (BOCA, 1993), which is now an HVAC standard included in the Massachusetts State 
9

Building Code (SBBRS, 1997). According to the NAAQS, carbon monoxide levels in outdoor 
air should not exceed 9 ppm in an eight-hour average (US EPA, 2006). 
Carbon monoxide should not be present in a typical, indoor environment . If it is present, 
indoor carbon monoxide levels should be less than or equal to outdoor levels. Outdoor carbon 
monoxide concentrations ranged from 1 to 2 ppm due to idling buses in front of the school 
(Table 1). Carbon monoxide levels measured inside the building were ND (Table 1). 
Particulate Matter (PM2.5) 
The US EPA has established NAAQS limits for exposure to particulate matter. 
Particulate matter is airborne solids that can be irritating to the eyes, nose and throat. The 
NAAQS originally established exposure limits to particulate matter with a diameter of 10 μm or 
less (PM10). According to the NAAQS, PM10 levels should not exceed 150 microgram per 
cubic meter (μg/m 3 ) in a 24-hour average (US EPA, 2006). These standards were adopted by 
both ASHRAE and BOCA. Since the issuance of the ASHRAE standard and BOCA Code, US 
EPA established a more protective standard for fine airborne particles. This more stringent 
PM2.5 standard requires outdoor air particle levels be maintained below 35 μg/m 3 over a 24-hour 
average (US EPA, 2006). Although both the ASHRAE standard and BOCA Code adopted the 
PM10 standard for evaluating air quality, MDPH uses the more protective PM2.5 standard for 
evaluating airborne particulate matter concentrations in the indoor environment. 
Outdoor PM2.5 concentrations were measured at 6 μg/m 3 at the time of the assessment 
(Table 1). PM2.5 levels measured in the school ranged from 2 to 19 μg/m 3 (Table 1). Both 
indoor and outdoor PM2.5 levels were below the NAAQS PM2.5 level of 35 μg/m 3 . Frequently, 
indoor air levels of particulates (including PM2.5) can be at higher levels than those measured 
outdoors. A number of mechanical devices and/or activities that occur in schools can generate 
10

particulate during normal operations. Sources of indoor airborne particulates may include but 
are not limited to particles generated during the operation of fan belts in the HVAC system, 
cooking in the cafeteria stoves and microwave ovens; use of photocopiers, fax machines and 
computer printing devices; operation of an ordinary vacuum cleaner and heavy foot traffic 
indoors. 
Volatile Organic Compounds 
Indoor air concentrations can be greatly impacted by the use of products containing 
volatile organic compounds (VOCs). VOCs are carbon-containing substances that have the 
ability to evaporate at room temperature. Frequently, exposure to low levels of total VOCs 
(TVOCs) may produce eye, nose, throat and/or respiratory irritation in some sensitive 
individuals. For example, chemicals evaporating from a paint can stored at room temperature 
would most likely contain VOCs. In an effort to identify materials that can potentially increase 
indoor VOC concentrations, BEH staff examined rooms for products containing these respiratory 
irritants. 
Cleaning products were found in rooms throughout the building. The type and brand of 
these products varied from room to room. Cleaning products contain chemicals that can be 
irritating to the eyes, nose and throat of sensitive individuals. These products should be properly 
labeled and stored in an area that is not accessible to children. Additionally, a Material Safety 
Data Sheet (MSDS) should be available at a central location for each product in the event of an 
emergency. Consideration should be given to providing teaching staff with school issued 
cleaning products and supplies to prevent any potential for adverse chemical interactions 
between residues left from cleaners used by the schools facilities staff and those left by cleaners 
brought in by others. 
11

Several classrooms contained dry erase boards and related materials. Materials such as 
dry erase markers and dry erase board cleaners may contain VOCs, such as methyl isobutyl 
ketone, n-butyl acetate and butyl-cellusolve (Sanford, 1999), which can be irritating to the eyes, 
nose and throat. 
Other Conditions 
Other conditions that can affect indoor air quality were observed during the assessment. 
In several classrooms, stored items were observed on windowsills, tabletops, counters, bookcases 
and desks. The large number of items stored in classrooms provides a source for dusts to 
accumulate. These items (e.g., papers, folders, boxes) make it difficult for custodial staff to 
clean. Items should be relocated and/or be cleaned periodically to avoid excessive dust build up. 
In addition, these materials can accumulate on flat surfaces (e.g., desktops, shelving and carpets) 
in occupied areas and subsequently be re-aerosolized causing further irritation. 
A number of univent/supply air diffusers, exhaust vents and personal fans in classrooms 
were observed to have accumulated dust/debris (Picture 22) . Re-activated supply vents/fans can 
aerosolize dust accumulated on fan blades/housing. If exhaust vents are not functioning, 
backdrafting can occur, which can re-aerosolize dust particles. 
Lastly, a classroom had a pet bird who was housed in a cage (Picture 23). Animal 
dander, fur and wastes can all be sources of respiratory irritants. Animal cages should be cleaned 
regularly to avoid the aerosolization of allergenic materials and/or odors. 
12

Conclusions/Recommendations 
In view of the findings at the time of the assessment, the following recommendations are 
made to improve indoor air quality: 
1. Operate all ventilation systems throughout the building continuously during periods of 
school occupancy. To increase airflow in classrooms, set univent controls to “high”. 
School staff should be encouraged not to deactivate classroom univents; rather, report 
any complaints to the facilities department. 
2. Inspect all exhaust motors and belts periodically for proper function. Repair and replace 
as necessary. 
3. Remove all blockages from univents and exhaust vents to ensure adequate airflow. 
4. Consider installing exhaust ventilation in work room. 
5. Use openable windows in conjunction with mechanical ventilation to increase air 
exchange. Care should be taken to ensure windows are properly closed at night and 
weekends to avoid the freezing of pipes and potential flooding. 
6. Duct exhaust vents away from fresh air intakes on exterior wall of modular classrooms. 
7. Clean accumulated dust and debris from fresh air intakes on exterior wall of modular 
classrooms. 
8. Consider adopting a balancing schedule of every 5 years for all mechanical ventilation 
systems, as recommended by ventilation industrial standards (SMACNA, 1994). 
9. Change filters for air-handling equipment (e.g., univents, AHUs and ACs) as per the 
manufacturer’s instructions or more frequently if needed. Vacuum interior of units prior 
to activation to prevent the aerosolization of dirt, dust and particulates. Ensure filters fit 
13

flush in their racks with no spaces in between allowing bypass of unfiltered air into the 
unit. 
10. For buildings in New England, periods of low relative humidity during the winter are 
often unavoidable. Therefore, scrupulous cleaning practices should be adopted to 
minimize common indoor air contaminants whose irritant effects can be enhanced when 
the relative humidity is low. To control for dusts, a high efficiency particulate arrestance 
(HEPA) filter equipped vacuum cleaner in conjunction with wet wiping of all surfaces is 
recommended. Avoid the use of feather dusters. Drinking water during the day can help 
ease some symptoms associated with a dry environment (throat and sinus irritations). 
11. Cut shrubs and trees in a manner to maintain a space of 3 feet from the building exterior 
and univent fresh air intakes, to prevent moisture from being held against exterior brick 
and moisture-laden air to be drawn in by the fresh air intake. 
12. Consider having exterior walls re-pointed and waterproofed to prevent water intrusion. 
This measure should include a full building envelope evaluation. 
13. Repair any existing water leaks and replace any remaining water-damaged ceiling tiles. 
Examine the area above these tiles for mold growth. Disinfect areas of water leaks with 
an appropriate antimicrobial, as needed. 
14. Move plants away from univents in classrooms. Avoid over-watering and examine drip 
pans periodically for mold growth. Disinfect with an appropriate antimicrobial where 
necessary. 
15. Clean and maintain aquariums and animal cages to prevent mold growth and associated 
odors. 
14

16. Store cleaning products properly and out of reach of students. All cleaning products used 
at the facility should be approved by the school department with MSDS’ available at a 
central location. 
17. Relocate or consider reducing the amount of materials stored in classrooms to allow for 
more thorough cleaning of classrooms. Clean items regularly with a wet cloth or sponge 
to prevent excessive dust build-up. 
18. Clean accumulated dust and debris periodically from univent air diffusers, exhaust vents 
and blades of personal fans. 
19. Consider adopting the US EPA (2000) document, “Tools for Schools”, as an instrument 
for maintaining a good indoor air quality environment in the building. This document is 
available at: http://www.epa.gov/iaq/schools/index.html . 
20. Refer to resource manual and other related indoor air quality documents located on the 
MDPH’s website for further building-wide evaluations and advice on maintaining public 
buildings. These documents are available at: http://mass.gov/dph/iaq . 
15

References 
ACGIH. 1989. Guidelines for the Assessment of Bioaerosols in the Indoor Environment. 
American Conference of Governmental Industrial Hygienists, Cincinnati, OH. 
ASHRAE. 1989. Ventilation for Acceptable Indoor Air Quality. American Society of Heating, 
Refrigeration and Air Conditioning Engineers. ANSI/ASHRAE 62-1989. 
BOCA. 1993. The BOCA National Mechanical Code/1993. 8 th ed. Building Officials & Code 
Administrators International, Inc., Country Club Hills, IL. 
Lstiburek, J. & Brennan, T. 2001. Read This Before You Design, Build or Renovate. Building 
Science Corporation, Westford, MA. U.S. Department of Housing and Urban Development, 
Region I, Boston, MA 
MDPH. 1997. Requirements to Maintain Air Quality in Indoor Skating Rinks (State Sanitary 
Code, Chapter XI). 105 CMR 675.000. Massachusetts Department of Public Health, Boston, 
MA. 
OSHA. 1997. Limits for Air Contaminants. Occupational Safety and Health Administration. 
Code of Federal Regulations. 29 C.F.R 1910.1000 Table Z-1-A. 
Sanford. 1999. Material Safety Data Sheet (MSDS No: 198-17). Expo  Dry Erase Markers 
Bullet, Chisel, and Ultra Fine Tip. Sanford Corporation. Bellwood, IL. 
SBBRS. 1997. Mechanical Ventilation. State Board of Building Regulations and Standards. 
Code of Massachusetts Regulations. 780 CMR 1209.0 
SMACNA. 1994. HVAC Systems Commissioning Manual. 1 st ed. Sheet Metal and Air 
Conditioning Contractors’ National Association, Inc., Chantilly, VA. 
US EPA. 2000. Tools for Schools. Office of Air and Radiation, Office of Radiation and Indoor 
Air, Indoor Environments Division (6609J). EPA 402-K-95-001, Second Edition. 
http://www.epa.gov/iaq/schools/tools4s2.html . 
US EPA. 2001. “Mold Remediation in Schools and Commercial Buildings”. Office of Air and 
Radiation, Indoor Environments Division, Washington, DC. EPA 402-K-01-001. March 2001. 
Available at: http://www.epa.gov/iaq/molds/mold_remediation.html . 
US EPA. 2006. National Ambient Air Quality Standards (NAAQS). US Environmental 
Protection Agency, Office of Air Quality Planning and Standards, Washington, DC. 
http://www.epa.gov/air/criteria.html . 
16

Picture 1 
Classroom Univent 
Picture 2 
Univent Fresh Air Intake on Exterior Wall

Picture 3 
Stored Items on Top and in Front of Univent, Note Panel Removed 
Picture 4 
Exhaust Vent on Ceiling

Picture 5 
Exhaust Vent on Wall 
Picture 6 
Exhaust Vent in Storage Closet

Picture 7 
Exhaust Vent in Classroom Shelving 
Picture 8 
Air Handling Unit on Wall in Modular Classroom 
Air Diffuser at Top, Exhaust Vent at Base

Picture 9 
Air Intake Directly Above Exhaust Vent on Exterior Wall 
Picture 10 
Accumulated Dust and Debris on Air Intake

Picture 11 
Air Conditioner in Window 
Picture 12 
Air Conditioner Ducted to Window by Hoses

Picture 13 
Shrubs Growing Against Building 
Picture 14 
Shrubs Growing Against Building

Picture 15 
Plants and Shrubs Growing in Front of Fresh Air Intake 
Picture 16 
Plants Growing in Front of Fresh Air Intake

Picture 17 
Shrubs Growing near Fresh Air Intake 
Picture 18 
Water Stains on Exterior Brick and Storage Shed

Picture 19 
Water Stains on Exterior Brick 
Picture 20 
Plants in Classrooms

Picture 21 
Aquarium in Classrooms 
Picture 22 
Accumulated Dust and Debris on Fan Blades

Picture 23 
Bird in Classroom

Location: Winthrop Elementary School Indoor Air Results
Address: 65 Central Street, Ipswich, MA Table 1 Date: 6 – 12 – 2009 
Location/ 
Room 
Occupants 
in Room 
Temp 
(°F) 
Relative 
Humidity 
(%) 
Carbon 
Dioxide 
(ppm) 
Carbon 
Monoxide 
(ppm) 
PM2.5 
(μg/m 3 ) 
Windows 
Openable 
Ventilation 
Remarks Supply Exhaust 
outside school 
A.M. 62 80 442 1 – 2 6 Overcast; Buses idling about to 
leave 
outside school 
P.M. 64 90 398 ND 13 Light rain 
Library 3 66 67 545 ND 3 Y UV off Y Stored items on UV; Exhaust 
vent dusty; PF; plants; CPs 
Title I 2 66 67 531 ND 4 Y Y Y 
Stored items on and in front of 
UV, UV panel open; window 
AC; PF 
2 23 69 73 879 ND 9 Y Y Y Stored items on UV 
3 25 70 73 1084 ND 19 1 of 3 open UV off Y DEM; PF; exterior door; indoor 
recess 
4 0 69 70 759 ND 8 Y Y Y Plants near UV; PFs 
5 0 68 72 678 ND 8 Y Y Y 
Stored items and furniture 
blocking UV; exterior door; 
DEM 
6 1 69 70 778 ND 10 Y Y Y Stored items and furniture 
blocking UV; DO 
ppm = parts per million CF = ceiling fan DO = door open PF = personal fan
μg/m 3 = micrograms per cubic meter CP = cleaning product MT = missing ceiling tile TB = tennis balls
AC = air conditioner CT = ceiling tile ND = non detect UF = upholstered furniture
AHU = air handling unit DEM = dry erase materials PC = photocopier UV = univent
aqua. = aquarium WD = water-damaged 
Comfort Guidelines 
Carbon Dioxide: < 600 ppm = preferred Temperature: 70 - 78 °F
600 - 800 ppm = acceptable Relative Humidity: 40 - 60%
> 800 ppm = indicative of ventilation problems Particle matter 2.5 < 35 ug/m 3 
Table 1, page 1

Location: Winthrop Elementary School Indoor Air Results
Address: 65 Central Street, Ipswich, MA Table 1 (continued) Date: 6 – 12 – 2009 
Location/
Room Occupants
in Room
Temp
(°F)
Relative
Humidity
(%)
Carbon
Dioxide
(ppm)
Carbon
Monoxide
(ppm)
PM2.5
(μg/m 3 ) Windows
Openable
Ventilation
Remarks Supply Exhaust 
7 25 69 73 1018 ND 10 Y Y Y UV blocked by table; CPs; 
DEM; DO; exterior door 
8 25 69 71 819 ND 6 Y UV off Y Water cooler; UF; DO 
9 1 69 70 924 ND 11 Y UV off Y Aqua; window AC; TB 
11 9 68 67 822 ND 5 Y Y Y Stored items and PF on UV 
13 17 68 67 781 ND 7 Y Y Y Stored items on and in front of 
UV; window AC; water cooler 
14 22 69 68 945 ND 12 Y Y Y Stored items on UV; CPs; Aqua; 
DO 
15 3 68 68 945 ND 6 Y Y Y Aqua; plants; DO; Bird Cage 
16 0 68 67 852 ND 9 Y Y Y CPs 
17 2 69 65 589 ND 8 Y UV off Y DEM; DO 
ppm = parts per million CF = ceiling fan DO = door open PF = personal fan
μg/m 3 = micrograms per cubic meter CP = cleaning product MT = missing ceiling tile TB = tennis balls
AC = air conditioner CT = ceiling tile ND = non detect UF = upholstered furniture
AHU = air handling unit DEM = dry erase materials PC = photocopier UV = univent
aqua. = aquarium WD = water-damaged 
Comfort Guidelines 
Carbon Dioxide: < 600 ppm = preferred Temperature: 70 - 78 °F
600 - 800 ppm = acceptable Relative Humidity: 40 - 60%
> 800 ppm = indicative of ventilation problems Particle matter 2.5 < 35 ug/m 3 
Table 1, page 2

Location: Winthrop Elementary School Indoor Air Results
Address: 65 Central Street, Ipswich, MA Table 1 (continued) Date: 6 – 12 – 2009 
Location/
Room Occupants
in Room
Temp
(°F)
Relative
Humidity
(%)
Carbon
Dioxide
(ppm)
Carbon
Monoxide
(ppm)
PM2.5
(μg/m 3 ) Windows
Openable
Ventilation
Remarks Supply Exhaust 
18 10 70 65 732 ND 10 Y Y Y WD CTs; DO; PF 
19 26 70 66 913 ND 12 Y Y Y UV blocked by books and 
furniture; DO 
20 25 70 65 968 ND 12 Y Y Y UV blocked by furniture; PF; 
DEM; DO 
21 3 70 64 794 ND 11 Y Y Y UV blocked by furniture; DEM; 
PF 
22 20 70 67 989 ND 19 Y Y Y PF 
23 24 70 66 1059 ND 14 Y Y Y UV blocked by furniture 
24 23 69 68 798 ND 9 Y Y Y UV blocked in front; CPs; UF; 
AD; DEM 
25 15 68 67 775 ND 19 Y Y Y Stored items on and in front of 
UV; PF 
26 Art 1 68 65 508 ND 5 Y Y Y WD CTs; Kiln with local 
exhaust 
ppm = parts per million CF = ceiling fan DO = door open PF = personal fan
μg/m 3 = micrograms per cubic meter CP = cleaning product MT = missing ceiling tile TB = tennis balls
AC = air conditioner CT = ceiling tile ND = non detect UF = upholstered furniture
AHU = air handling unit DEM = dry erase materials PC = photocopier UV = univent
aqua. = aquarium WD = water-damaged 
Comfort Guidelines 
Carbon Dioxide: < 600 ppm = preferred Temperature: 70 - 78 °F
600 - 800 ppm = acceptable Relative Humidity: 40 - 60%
> 800 ppm = indicative of ventilation problems Particle matter 2.5 < 35 ug/m 3 
Table 1, page 3

Location: Winthrop Elementary School Indoor Air Results
Address: 65 Central Street, Ipswich, MA Table 1 (continued) Date: 6 – 12 – 2009 
Location/
Room Occupants
in Room
Temp
(°F)
Relative
Humidity
(%)
Carbon
Dioxide
(ppm)
Carbon
Monoxide
(ppm)
PM2.5
(μg/m 3 ) Windows
Openable
Ventilation
Remarks Supply Exhaust 
27 22 68 68 856 ND 18 Y UV off Y DEM; carpet 
Gym 0 67 73 633 ND 13 4 of 4 open 1 of 2 UV 
off Y 
Physical 
Therapy 1 68 73 628 ND 7 Y Y Y Exhaust blocked; AC 
Nurse 1 68 73 738 ND 9 Y N N 
Cafeteria 64 68 75 654 ND 11 Y Y CPs; CFs; exterior door 
Main office 2 68 72 631 ND 8 Y N N Wall AC; plants 
Work room 3 67 72 613 ND 8 N N N 3 PCs; DO; passive vent in door 
Music 0 68 58 463 ND 2 Y Y Y PF; DEM 
Band Practice 0 68 58 459 ND 2 Y N N 2 DO 
ppm = parts per million CF = ceiling fan DO = door open PF = personal fan
μg/m 3 = micrograms per cubic meter CP = cleaning product MT = missing ceiling tile TB = tennis balls
AC = air conditioner CT = ceiling tile ND = non detect UF = upholstered furniture
AHU = air handling unit DEM = dry erase materials PC = photocopier UV = univent
aqua. = aquarium WD = water-damaged 
Comfort Guidelines 
Carbon Dioxide: < 600 ppm = preferred Temperature: 70 - 78 °F
600 - 800 ppm = acceptable Relative Humidity: 40 - 60%
> 800 ppm = indicative of ventilation problems Particle matter 2.5 < 35 ug/m 3 
Table 1, page 4

Location: Winthrop Elementary School Indoor Air Results
Address: 65 Central Street, Ipswich, MA Table 1 (continued) Date: 6 – 12 – 2009 
Location/
Room Occupants
in Room
Temp
(°F)
Relative
Humidity
(%)
Carbon
Dioxide
(ppm)
Carbon
Monoxide
(ppm)
PM2.5
(μg/m 3 ) Windows
Openable
Ventilation
Remarks Supply Exhaust 
Speech 0 68 60 468 ND 3 Y Y Y DEM 
ppm = parts per million CF = ceiling fan DO = door open PF = personal fan
μg/m 3 = micrograms per cubic meter CP = cleaning product MT = missing ceiling tile TB = tennis balls
AC = air conditioner CT = ceiling tile ND = non detect UF = upholstered furniture
AHU = air handling unit DEM = dry erase materials PC = photocopier UV = univent
aqua. = aquarium WD = water-damaged 
Comfort Guidelines 
Carbon Dioxide: < 600 ppm = preferred Temperature: 70 - 78 °F
600 - 800 ppm = acceptable Relative Humidity: 40 - 60%
> 800 ppm = indicative of ventilation problems Particle matter 2.5 < 35 ug/m 3 
Table 1, page 5